Burners

SINGLE BURNERS JET

This is a high-speed burner type “mixing nozzle”, the oxidizer and fuel are mixed in the combustion head. Produce a tense flame that allows penetration of the heat in the combustion chamber.
Burners JET can be used both in cooking chambers with fiber insulation, which a refractory insulating material or dense low density.
They can be of two types, lateral burner or ceiling burner.
The ignition burner JET mainly by high voltage discharge electrode provided by a plug, can also be applied a system for igniting a pilot flame.
Flame detection is performed by a special electrode, but you can use the UV photoelectric cell. The flame detection systems are required on all burners operating at temperatures below 750 °C.

Burners JET can operate with different combustion regimes depending on the application: On-Off with power ratio equal to 1:20, the pulse using the valve to the gas metering and pneumatic control of the combustion air or modular valve with combustion air control is using a motorized valve and gas dosing with the valve.

Burners JET can also operate with the combustion air preheated to 400 ° C with the advantage of having a high flame temperature and thus lower fuel consumption, but with a slight elevation values NOx.

Download technical data sheet (.pdf)

BR-70JET-VG
Ceiling burner, gas fuel
BR-70JET-VG

BR-70JET-LG
Lateral inclusion, gas fuel
BR-70JET-LG

PARAMETER NATURAL GAS PROPANE BUTANE
Maximum Input (kW) 81,5 81,5 81,5
Rated Input (kW) 70,0 70,0 70,0
Minimum Input (kW) 17,0 17,0 17,0
Maximum Temperature (°C) 1000 1000 1000
Maximum Flame Velocity (m/s) 220
High Fire Flame Length (mm) 750 600 600

BR-70JET-LG-PLUS
Ceiling burner, gas fuel
BR-70JET-LG-PLUS

PARAMETER NATURAL GAS PROPANE BUTANE
Maximum Input (kW) 81,5 81,5 81,5
Rated Input (kW) 70,0 70,0 70,0
Minimum Input (kW) 17,0 17,0 17,0
Maximum Temperature (°C) 1200 1200 1200
Maximum Flame Velocity (m/s) 200
High Fire Flame Length (mm) 680 500 500

BR-95JET-VG
Ceiling burner, gas fuel, with controlled ignition
BR-95JET-VG

BR-95JET-LG
Lateral burner, gas fuel, with controlled ignition
BR-95JET-LG

PARAMETER NATURAL GAS PROPANE BUTANE
Maximum Input (kW) 100 100 100
Rated Input (kW) 95 95 95
Minimum Input (kW) 15 15 15
Maximum Temperature (°C) 1250 1250 1250
Maximum Flame Velocity (m/s) 220
High Fire Flame Length (mm) 860 780 780

BR-105JET-VG
Ceiling burner, gas fuel, with controlled ignition
BR-105JET-VG

BR-105JET-LG
Lateral burner, gas fuel, with controlled ignition
BR-105JET-LG

PARAMETER NATURAL GAS PROPANE BUTANE
Maximum Input (kW) 122 122 122
Rated Input (kW) 105 105 150
Minimum Input (kW) 15 15 15
Maximum Temperature (°C) 1100 1100 1100
Maximum Flame Velocity (m/s) 220
High Fire Flame Length (mm) 860 780 780

BR-220JET-LG
Lateral burner, gas fuel, with controlled ignition
BR-220JET-LG

PARAMETER NATURAL GAS PROPANE BUTANE
Maximum Input (kW) 255 255 255
Rated Input (kW) 220 220 220
Minimum Input (kW) 20 20 20
Maximum Temperature (°C) 1250 1250 1250
Maximum Flame Velocity (m/s) 200
High Fire Flame Length (mm) 910 800 800

BR-70JET-VO
Ceiling burner, oil fuel
BR-70JET-VO

PARAMETER LIGHT OIL HEAVY OIL DIESEL
Maximum Input (kW) 81.5 81.5 81.5
Rated Input (kW) 70.0 70.0 70.0
Minimum Input (kW) 17.0 17.0 17.0
Maximum Temperature (°C) 1000 1000 1000
Maximum Flame Velocity (m/s) 140
High Fire Flame Length (mm) 480 600 400

BR-100JET-VO
Ceiling burner, oil fuel
BR-100JET-VO

PARAMETER LIGHT OIL HEAVY OIL DIESEL
Maximum Input (kW) 120 120 120
Rated Input (kW) 100 100 100
Minimum Input (kW) 20 20 20
Maximum Temperature (°C) 1000 1000 1000
Maximum Flame Velocity (m/s) 180
High Fire Flame Length (mm) 520 680 480

BR-70JET-4 (RATIO 1-3/1-4)
Ceiling burner, oil fuel, mechanical pulverization
BR-70JET-4

PARAMETER LIGHT OIL HEAVY OIL DIESEL
Maximum Input (kW) 110 110 110
Rated Input (kW) 70.0 70.0 70.0
Minimum Input (kW) 17.0 17.0 17.0
Maximum Temperature (°C) 1000 1000 1000
Maximum Flame Velocity (m/s) 48 48 48
High Fire Flame Length (mm) 2800 2800 2800

BR-T8
Ceiling burner, oil fuel, with controlled ignition
BR-T8

PARAMETER LIGHT OIL HEAVY OIL DIESEL
Maximum Input (kW) 150 150 150
Rated Input (kW) 105 105 105
Minimum Input (kW) 25 25 205
Maximum Temperature (°C) 1000 1000 1000
Maximum Flame Velocity (m/s) 180
High Fire Flame Length (mm) 520 680 480

BR-LATERALE
Lateral burner, oil fuel, with controlled ignition
BR-LATERALE

PARAMETER LIGHT OIL HEAVY OIL DIESEL
Maximum Input (kW) 250 250 250
Rated Input (kW) 220 220 220
Minimum Input (kW) 25 25 25
Maximum Temperature (°C) 1000 1000 1000
Maximum Flame Velocity (m/s) 140
High Fire Flame Length (mm) 480 600 400

Multiple Burners

High speed burners used with all gaseous fuels.
Lateral installation with flame or no-flame control, to use in areas with lower or higher temperatures compared to the controlled ignition temperature of the fuel.
Flame control made with electrodes or photocells.

BR-F-JET-LG
Kiln Lateral Burner
Lateral burner, gas fuel, with controlled ignition
BR-F-JET-LG

PARAMETER VALUE
Maximum Input (kW) 765
Rated Input (kW) 660
Minimum Input (kW) 60
Maximum Temperature (°C) 1250
Fuel Natural Gas, Propane, Butane

BR-F-JET-VG-CA
Kiln Ceiling Burner
Ceiling burner, gas fuel, with controlled ignition
BR-F-JET-VG-CA

PARAMETER VALUE
Maximum Input (kW) 1050
Rated Input (kW) 950
Minimum Input (kW) 170
Maximum Temperature (°C) 1000
Fuel Natural Gas, Propane, Butane

BR-F-JET-VG-AA
Kiln Ceiling Burner
Ceiling burner, gas fuel
BR-F-JET-VG-AA

PARAMETER VALUE
Maximum Input (kW) 800
Rated Input (kW) 700
Minimum Input (kW) 170
Maximum Temperature (°C) 1000
Fuel Natural Gas, Propane, Butane

BR-LATERALE
Kiln Lateral Burner
Lateral burner, oil fuel, with auto-ignition
BR-LATERALI-MULTIPLI

PARAMETER VALUE
Maximum Input (kW) 1400
Rated Input (kW) 1000
Minimum Input (kW) 170
Maximum Temperature (°C) 1000
Fuel Heavy oil, Light oil, Diesel

BR-F-JET-VO-AA-PLUS
Kiln Ceiling Burner
Ceiling burner, oil fuel, auto-ignition
BR-F-JET-VO-AA-PLUS

PARAMETER VALUE
Maximum Input (kW) 2100
Rated Input (kW) 1400
Minimum Input (kW) 340
Maximum Temperature (°C) 1000
Fuel Heavy oil, Light oil, Diesel

BR-E-JET-VO-AA
Kiln Ceiling Burner
Ceiling burner, oil fuel, with continuous pulses
BR-E-JET-VO-AA

PARAMETER VALUE
Maximum Input (kW) 1630
Rated Input (kW) 1400
Minimum Input (kW) 340
Maximum Temperature (°C) 1000
Fuel Heavy oil, Light oil, Diesel

BR-F-JET-4 (RATIO 1-3/1-4)
Kiln Ceiling Burner
Ceiling burner, oil fuel, with pulses
BR-F-JET-4

PARAMETER VALUE
Maximum Input (kW) 1100
Rated Input (kW) 700
Minimum Input (kW) 170
Maximum Temperature (°C) 1000
Fuel Heavy oil, Light oil, Diesel

BR-S.F.B.
Ceiling burner, solid fuels
BR-E-JET-VO-AA

PARAMETER COAL (PET COKE) SAWDUST (WOOD) POMACE OIL (OLIVES)
Maximum Input (kW) 1100 1100 1100
Rated Input (kW) 770 770 770
Minimum Input (kW) 170 170 170
Maximum Temperature (°C) 1000 1000 1000

BURNERS – Grinding System

Grinding, storage and distribution plant of solid fuels
Different kind of burners for solid fuel kilns:

  • Fuel grinding and distribution system
  • Electronically dosage control system
  • Auto-ignition burners for combustion zone
  • Heads burners specifically designed to optimize combustion
  • Compatible with charcoal and fuels of vegetable origin (biomass)
  • Different powers available for all ceramic industry applications

Download technical data sheet (.pdf)

GRINDING SYSTEM

CASE HISTORIES

San Marco -Terreal (Italy)

Read More
Sarl Banou Messaud (Algeria)

Read More
Pratigliolmi – Cotto Nobile di Toscana (Italy)

Easymud line

Read More

NEWSLETTER

Subscribe now!

Subscribe

IN THE WORLD

WORK WITH US

Send now your CV...

Read More
Back to top